Software SetupBACnet Manager
1. Run the BACnet Manager application by clicking on the desktop
shortcut to the menu item under the BaseManager folder in
ProgramsUnblock Firewall if prompted.
2. Review the Status tab on the BacManager window and verify
that the BaseStation 3200 controllers have been processed.
BACnet Objects
1. The BACnet Network Number = 444
2. Connection = BACnet/IP
3. BaseStation 3200 Controller Object Model:
a. Accumulator Objectone for each flow device. This
reports the accumulated water used for the flow device.
This is updated daily.
b. Analog Inputone for each flow device. This reports the
water used for the previous day. This is updated daily.
c. Binary Inputthere are nine of these and they each
represent an alert state for the controller:
- Upper Flow Shutdown
- Two-wire High Current Shutdown
- High Temperature Shutdown (not used)
- Watering Paused
- Failure to Connect
- Dial Set To OFF
- Valve Failure
- Device Failure (unable to communicate)
- Program Overrun
d. Devicethis represents the 3200 controller
1-866-294-5847 Rev 11.19.2012 www.baselinesystems.com